PYK 4 SLD
Manufacturer Code: A0307259
6,08 € without VAT 7,36 € with VAT
PYK 4 SLD
Rated cross-section | 4 mm² (12 AWG) |
Connection range | 0,25 ÷ 6 mm² (22 ÷ 10 AWG) |
Rated current [A] CE | 10 |
Rated current [A] UL | 10 |
Rated impulse withstand voltage Uimp [V] | 6000 |
Rated voltage or operating voltage range [V] | 24 DC |
Signaling current - current through the signaling circuit when the fuse is broken | 1 mA (for 12V) / 2,2 mA (for 24V) |
Tool for conductor release | Flat screwdriver 0,5 x 3 |
Assembly method | TH 35 |
Pollution degree | 3 |
IP code | 20 |
Operating temperature [°C] | -40 ÷ +100 |
Number of clamping points per level / Number of levels | 2 / 1 |
End cover plate required: | NO |
Size of fuse-link | 5 x 20 |
Testing | EN 60947-7-3 |
Dimensions [mm] (width / height / length) | 8 / 61,1 / 63,1 |
Weight [g] | 19 |
Packing [pcs] | 15 |
Solid conductor [mm²] | 0,34 ÷ 6 |
Finely stranded conductor with sleeve [mm²] | 0,25 ÷ 4 |
Stripping length [mm] | 9 ÷ 10 |
Note | In the case of mounting a sleeve on a Cu conductor with a special treatment, the connection is slippery, the conductor treated in this way may not pass the static tensile test. |